← Back to the monthly list · Siemens →
CVE-2026-63353 Siemens · SIMATIC Drive Controller CPU 1504D TF
AI summary
Siemens SIMATIC Drive Controller CPU 1504D TF does not sanitize comment fields in imported trace files rendered on the Trace page. If an attacker tricks a user with the “Read diagnostics” right into importing a crafted file, JavaScript can run in their browser and perform PLC operations within the user's authorization. Critical (CVSS 9.6), not known to be exploited.
Official description
Affected devices do not properly sanitize comment fields contained in imported trace files before rendering them on the Trace page. This could allow an attacker to social engineer an authorized user who holds the function right “Read diagnostics” into importing a specially crafted trace file. Successful exploitation could allow attacker-controlled JavaScript to execute in the user’s browser session and perform PLC operations through the web server within the scope of the user’s authorization.
- Published
- 2026-10-13 10:17 UTC
- Modified
- 2026-10-15 20:38 UTC
- CVSS
- 9.6 Critical
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H - EPSS
- 0.45% (percentile 31)
- ENISA EUVD
- EUVD-2026-98384
- CISA SSVC
- Exploitation: none · Automatable: no · Technical impact: total
- CWE
- CWE-79
- Category
- Industrial / OT
CVSS vector
- Attack vector
- network
- Attack complexity
- low
- Privileges required
- none
- User interaction
- required
- Scope
- changed
- Confidentiality
- high
- Integrity
- high
- Availability
- high
References
- NVD · CVE.org
- cert-portal.siemens.com
https://cert-portal.siemens.com/productcert/html/ssa-591731.html